ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/4,
1
/2 DIN and fieldmount 7 Advanced Level
68 IM/CM/ED–EN Rev. X
…Profile Parameters / …Common Settings
Segment Options
G'teed Ramp/Soak Enables the Guaranteed Ramp/Soak (Holdback) function. When enabled (On), the
relevant configuration frames are displayed in Program / Segment menus to allow the
Guaranteed Ramp/Soak function to be configured.
Events 1 to 8 Enables the Segment Event function. When enabled (On), the relevant configuration
frame is displayed for each segment to allow the Segment Events to be configured.
PV Event Enables the PV Event function. When enabled (On), the relevant configuration frames are
displayed in the Program / Segment menus to allow the PV Event to be configured.
Timed Event Enables the Timed Event function. When enabled (On), the relevant configuration frames
are displayed for each segment to allow the Timed Event to be configured.
User Value Enables the User Value function. When enabled (On), the relevant frames are displayed
to allow the User Value function to be configured.
Retort Function Enables the Retort function. When enabled (On), the relevant frames are displayed to
configure the Retort function.
Continue
Continues to the next segment.
Repeat Segment
Repeats the current segment.
PV Event Trip The PV Event Trip value used to determine the PV Event status for each segment. The
value is set in PV engineering units.
Note. Available only if the PV Event functionality is enabled in the Segment Options
menu.
User Value Limits
Default Value The default value that the User Value will be set to when a program is not running.
Note. User Value menu only available if the User Value functionality has been enabled in
the Segment Options menu.
Low Limit The Low Limit parameter is used to set the minimum User Value value that may be
entered for each segment.
High Limit The High Limit parameter is used to set the maximum User Value value that may be
entered for each segment.
Fast Run Mode This frame enables a mode that allows the profile program to be run 8 times faster than
the programmed times. In this mode guaranteed Ramp / Soak settings are ignored but
wait conditions are not overridden.