II K 6-6
Operating Instructions
Drive control from the panel
CAUTION: Appropriate safety precautions must be taken
before starting the drive.
Before the drive can be controlled from the panel, the panel first
must be given permission to take control. The panel’s ability to
control the drive is determined by the Panel Lock function which
can be accessed through menu selection and by the LOC/REM
key provided on the panel. The Panel Lock mode must be set to
unlocked or no par write, since all other entries will prevent the
panel from taking control of the drive. The LOC/REM key is used
to actually transfer control to the panel. This is then signaled by
the LOC status indication in the status line. Pressing the key
once again will cause the panel to give up its command of the
drive, and the LOC indication in the status line will disappear.
Actual value display
In the first line of the panel display, the actual values selected
with the parameters Panel Act 1 (6.16) to Panel Act 3 (6.18) are
indicated. The desired actual values have to be defined before-
hand with these parameters. When the drive is being controlled
from the panel, the actual values are continually updated.
Reference display
In this line, the speed reference set by means of the UP/DOWN
keys is displayed.
Status display
LOC in the status line indicates that the drive is being controlled
from the panel.
RUN in der status line indicates that the drive is switched on and
enabled.
Activate reference
Any modification of a reference value has to be initiated by
pressing the ENTER key, which will result in the reference value
displayed being
underlined. The desired reference value is then
set using the UP/DOWN keys.
Change reference
A reference value can be changed only when it is displayed with
an underline. Using the UP/DOWN keys, you can set any speed
reference between 0 rpm and the maximum speed defined with
the parameter Max Speed (1.06).
Drive ON and START, Drive OFF and STOP
CAUTION: Appropriate safety precautions must be taken
before starting the drive.
The function of this key is dependent on the current drive status.
If the drive is in the OFF state, pressing this key will switch ON
the line contactor and enable the controller. The drive will the
accelerate in accordance with the preset ramp time (5.09) up to
the selected speed reference.
If the drive is in the ON state, pressing this key will stop the drive.
The drive will then decelerate in accordance with the preset stop
mode (2.03) and ramp time (5.10, if activated) and will switch
OFF the line contactor.
Change reference polarity
The polarity of the speed reference indicated in the reference
display can be changed by pressing this key. The motor will first
decelerate and then accelerate - only in 4Q applications - in the
reverse direction.
Reset (Fault acknowledgement)
All faults detected by the converter can be reset by simply
pressing this key, provided that the faults concerned are no
longer active.
Panel mode: Drive control
(17(5
0(18
/2&
5(0
5(6(7
1500rpm
440V 368A 1500rpm
OUTPUT MENU AUTO OFF HAND REM LOC <RUN>
$%%
(17(5
0(18
/2&
5(0
5(6(7
/2&
5(0
1500rpm
440V 368A 1500rpm
OUTPUT MENU AUTO OFF HA ND REM LOC <RUN>
/2&
5(0
Actual value display
Reference display
Status display
Activate reference
Drive ON and START
Drive STOP and OFF
Change reference polarity
Change reference
Drive control via panel
LOC = local (Panel)
REM = remote (Terminals/Fieldbus Adapter)
Running
flashing = Warning
Fault
Reset
faults