II K 6-5
Operating Instructions
LCD Contrast
Press Arrows
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Commissioning
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Change the LCD contast by using the keys.
The result will be shown immediately.
See chapter: Guided commissioning
Panel Lock
LCD Contrast
Commissioning
Disabled if the drive is in ON-state.
ðTransfer of param-
eters from drive to
the panel.
ðCancel function, no
transfer of param-
eters to the panel
Copies all drive param-
eters into the panel.
Should be the last ac-
tion after commission-
ing.
Copy to Panel
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Overwrite Panel?
No
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Yes
Copy to Panel (not possible in LOCal mode)
ðTransfer of param-
eters from panel to
the drive.
ðCancel function, no
transfer of param-
eters to the drive.
Transfers all previous-
ly copied parameters
to the drive.
Copy to Drive
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Overwrite Drive?
No
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Yes
Copy to Drive (not possible in LOCal mode)
Disabled if the drive is in ON-state.
Long/Short Par List
Short
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Long
ðComplete parameter
list visible.
ðSwitches to short
parameter list.
Long/Short Par List
ðResets all parameters
to the factory set-
tings.
ðCancel function, no
reset of parameters.
Resets all parameters to
the factory settings.
Factory Setting
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Reset all Params?
No
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Yes
Factory Setting
Disabled if the drive is in ON-state.
Parameter
access
Functions Panel
buttons
Panel Lock State
Read
Write
Output Display
Set Typecode
Read fault logger
Factory Setting
Copy to Panel
Copy to Drive
Long/Short Par List
Panel Lock
LCD Contrast
Commissioning
Reset
LOC/REM , <-> , (I)
Unlocked
llllllllllllll
No Par Write
l
x
l
x
l
x
l
x
lll
x
ll
No Local
lllllllllll
x
l
x
Read Only
l
x
l
x
l
x
l
x
lll
x
l
x
Locked x x
l
x
l
xxxx
ll
x
l
x
l
= enabled during this lock state
x = disabled during this lock state
Enter PIN Code
0
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Before any change in the Panel Lock mode can
become effective, the PIN number (“400“) first has to
be entered.
Enter the PIN number using the
keys, then
press
(17(5
.
If the correct PIN number has been entered, the
Panel Lock mode can be changed.
If the PIN number entered is incorrect, the Panel
Lock mode can not be changed and the original
mode will still be displayed.
Panel Lock
unlocked
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
No Par Write
No Local
Read Only
Locked
ðParameter modification disabled
ðDrive control from panel disabled
ðParam. modification and drive control disabled
ðOnly display of actual values possible
Select the desired lock mode and press
(17(5
.
ðAll entries possible.