II K 7-12
Serial Interfaces
For detailed information please refer to the related
fieldbus adapter description.
In the case you need a fieldbus other than shown,
please contact your local ABB sales office. ABB is
continuously developing on new solutions.
DeviceNet (including parameter transfer)
Parameter Meaning Alternative settings Typical settings
8.01 Module Type 0 = Disable
1 = Fieldbus
2 = RS232-Port
3 = Panel-Port
4 = Res Fieldbus
1 = Fieldbus
8.02 MAC ID 0…63 63
8.03 Baudrate 0 = 125 kBd
1 = 250 kBd
2 = 500 kBd
0 = 125 kBd
8.04 Status 0 = Self Test
1 = No Connect
2 = Connected
3 = Timeout
4 = Dup. Mac. Err.
5 = Bus_Off
6 = Com. Error
7 = Wrong Asmbly
Read only (parameter).
The module shows value ’No
Connect’ after first power-up.
8.05 Profile Selection 0 = ABB Drives
1 = CSA 2.8/3.0
0 = ABB Drives
8.06 Poll Output Select 0 = Basic Speed 3 = Multiple Dataset
8.07 Poll/Cos Input Sel 1 = Transparent 3 = Multiple Dataset
8.08 Cos Data Output 2 = Parameters
3 = Multiple Dataset
3 = Multiple Dataset
8.09 Bit Strobe Output 0 = Basic Speed
1 = Transparent
2 = Parameters
0 = Basic Speed
8.10 DataSet Indexes 0 = FBA DSet 1
1 = FBA DSet 10
0 = FBA DSet 1
8.11 Speed Ref Scale 032767 1500
8.12 Speed Act Scale 032767 1500
8.13 ABB Drives Stop M. 0 = Coast Stop
1 = Ramp Stop
0 = Coast Stop
8.14 Ramp Stop Level 020.000 1000
8.15 No. of Dataset 12 2
Table 7.3/1: Parameter settings for the most commonly used fieldbus adapters