II K 7-9
Serial Interfaces
Parameter overview for the most commonly used
fieldbuses
For parameter setting, with the control panel, intially
switch to Long Par List, in the MENU selection, in
Profibus (including parameter transfer)
Parameter Meaning Alternative settings Typical settings
8.01 Module Type 0 = Disable
1 = Fieldbus
2 = RS232-Port
3 = Panel-Port
4 = Res Feldbus
Fieldbus
8.02 Profibus Mode 0 = FMS
1 = PPO1
Data transf. PLC to DCS
(DS1.1, 1.2+Par)
Data transf. DCS to PLC
(DS2.1, 2.2+Par)
2 = PPO2
Data transf. PLC to DCS
(DS1.1…1.3, 3.1…3.3 +Par)
Data transf. DCS to PLC
(DS2.1…2.3, 4.1…4.3 +Par)
3 = PPO3
Data transf. PLC to DCS
(DS1.1, 1.2)
Data transf. DCS to PLC
(DS2.1, 2.2)
4 = PPO4
Data transf. PLC to DCS
(DS1.1…1.3, 3.1…3.3)
Data transf. DCS to PLC
(DS2.1…2.3, 4.1…4.3)
1 = PPO1
8.03 Station Number 2…126 2
8.04 Baudrate 0 = 9,6 kBd
1 = 19,2 kBd
2 = 93,75 kBd
3 = 187,5 kBd
4 = 500 kBd
5 = 1,5 MBd
6 = Auto
6 = Auto
8.05 Number of Data Set Pairs 1 = if 8.02 = 1 or 3
2 = if 8.02 = 2 or 4
1 (8.02 = 1)
8.06 Data Set Offset 0…255 0 = no Offset
8.07 Cut Off Timeout 0…255 (20ms grid)
between NPBA-02 and
Master
30 = 600ms
8.08 Comm Profile 0 = ABB DRIVES
1 = CSA 2.8/3.0
0 = ABB DRIVES
order to make the parameters visible. Continue with
setting of the user specific parameters (bold typed).