II K 3-11
Technical data
20
0,1
1
10
100
0 50 100 150 200 250 300 350 400 450
I
F
U
F
[A]
[V]
220
1.5
0.3
16
Important note:
Nominal field voltage and field current of the motor has to be within the field
controller operating range. For application with constant field it is easy to
check:
Transfer values of field current and field voltage to the diagram and check
that the point of intersection is within the operating range.
Fig. 3.7/3 Operating area of field exciter 0.1...6 A
DCS 40x.0180...DCS 40x.1000
Fig. 3.7/4 Operating area of field exciter 0.3...20 A
Table 3.7/1:
Field voltage range related to
specified input voltage
System con- Field
nection voltage
range
U
Line
[V~] [V-]
230 50...237
380 50...392
400 50...413
415 50...428
440 50...440
460 50...440
480 50...440
500 50...440
For field weakening application do that check with
nominal values and minimal values. Both points of
intersection have to be within the operating range.
Depend on the converter use the right diagram
(6 A or 20 A)
e.g. DCS401.0045
Ue 310 V / Ie 0.3 A
è 6A diagram è ok
Depend on the converter use the right diagram
(6 A or 20 A)
e.g. DCS402.0050
Ue
nom
310 V / Ie
nom
0.4 A
è 6A diagram è ok
Ue
min
100 V / Ie
min
0.2 A
è 6A diagram è not ok, not to realize !
1
2
Example:
Fig. 3.7/5 Example of Field exciter operating range
6
0,01
0,1
1
10
0 50 100 150 200 250 300 350 400 450
I
F
U
F
[A]
[V]
220
4
0.1
0.5
0,01
1
10
0 50 100 150 200 250 300 350 400 450
I
F
U
F
[A]
[V]
0,1
out of operating range
2SHUDWLQJUDQJH
DCS 40x.0020...DCS 40x.0140