ABB Switzerland Ltd 1KHW001493-EN
Archive No.: Rev. Date:
Programming and Testing Instructions ETL600 Rel.1
- A 05-11-16
Responsible Department: Prepared: Approved: Distribution: Lang.: Page:
PTUKT 2005-09-13 H. Benninger 2005-11-16 C. Leeb - EN 1/37
Valid for: Derived from: Replaces: Classification-No.: File:
- 1KHL015940-EN - - 1KHW001493ae Programming
and Testing Instructions ETL600
Rel1.doc
Powerline Carrier Equipment: Series ETL600
Programming and Testing Instructions ETL600 Rel.1
This document describes programming and testing of powerline carrier equipment ETL640 and ETL680,
including the teleprotection system NSD600.
Contents
A Programming Instructions for the ETL600 Rel.1 Equipment 3
A.1 General 3
A.2 Create a configuration for the equipment using HMI600 3
A.3 Assemblies in racks P7LA and P7LC 3
A.4 Settings for basic equipment ETL640/680 4
A.5 Settings for alarm unit R1BC, if present 4
A.6 Settings for NSD600 interface G4AI, if present 4
A.7 Check board type at slot N45 5
A.8 Check license key on P4LT/P4LU 5
B Testing Instructions for the ETL600 Rel. 1 Equipment. 7
B.1 General 7
B.2 Check power supply B5LA/B5LC 7
B.3 Connect to the equipment, download configuration and prepare for tuning
& testing 8
B.4 Change configuration, if necessary 8
B.5 Transmitter 8
B.6 Receiver 9
B.7 Testing of R1BC, if present 11
B.8 Configure Real Time Clock (RTC) 11
B.9 Testing of NSD600 with interface G4AI, if present 12
B.10 Testing of O4LE, if present 13
B.11 Testing of the V.11 ports 19
B.12 Testing of the V.24 ports 19
B.13 Documentation 20
B.14 Manual reset 20
Sheet ETL600 System Settings.............................................................................. A1 - A4
Sheet ETL600 System Test report....................................................................... B1 - B11
Test conditions:
• Temperature range: 10 °C to 40 °C.
• The connections for the tests can be made either at the test sockets on the front of the
equipment or at the terminals.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. © ABB Switzerland Ltd