ETL600 System Test Report
_ EN B4/B11
HE
Test
No.
Test procedure
Test point
Permissible
value
Units
Test
result
B.9 Testing of NSD600 /
G4AI, if present
B.9.1 Inputs
N11N22N28N34N54N65N71
Input 1 IN1
Activate Input 1
Check LED IN1
Terminal,
(T…/1) – (T.../2)
LED IN1
U1, see
System settings
ON
V DC
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
N11N22N28N34N54N65N71
Input 2 IN2
Activate Input 2
Check LED IN2
Terminal,
(T…/3) – (T.../4)
LED IN2
U2, see
System settings
ON
V DC
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
N11N22N28N34N54N65N71
Input 3 IN3
Activate Input 3
Check LED IN3
Terminal,
(T…/5) – (T.../6)
LED IN3
U3, see
System settings
ON
V DC
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
N11N22N28N34N54N65N71
Input 4 IN4
Activate Input 4
Check LED IN4
Terminal,
(T…/7) – (T.../8)
LED IN4
U4, see
System settings
ON
V DC
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
B.9.2 Outputs
N11N22N28N34N54N65N71
Enforce action for
OUT1.
Check Output 1, OUT1:
Check LED OUT1
Terminal,
(T…/9) – (T.../10)
LED OUT1
Closed
ON
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
N11N22N28N34N54N65N71
Enforce action for
OUT2.
Check Output 2, OUT2:
Check LED OUT2
Terminal,
(T…/11) – (T.../12)
LED OUT2
Closed
ON
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
N11N22N28N34N54N65N71
Enforce action for
OUT3.
Check Output 3, OUT3:
Check LED OUT3
Terminal,
(T…/13) – (T.../14)
LED OUT3
Closed
ON
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
N11N22N28N34N54N65N71
Enforce action for
OUT4.
Check Output 4, OUT4:
Check LED OUT4
Terminal,
(T…/15) – (T.../16)
LED OUT4
Closed
ON
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
N11N22N28N34N54N65N71
Enforce action for
relay 1
REL1 close/open
Check LED REL1
Terminal,
(T…/17) – (T.../18)
LED REL1
Refer G4AI
programming
ON
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
N11N22N28N34N54N65N71
Enforce action for
relay 2
REL2 close/open
Check LED REL2
Terminal,
(T…/19) – (T.../20)
LED REL2
Refer G4AI
programming
ON
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
B.9.3 NSD600 loop test
TPE1 TPE2
Check Actual
transmission time T
Link
Menu: Equipment,
Commissioning and
maintenance, NSD600
send loop test
HMI600
< 1.3*T0
ms
_______
_______
© ABB Switzerland Ltd Form 1KHW001493-EN