Appendix A – PROFIdrive parameters 187
945 R Array[64]
Unsigned16
Fault code (coded according to
DRIVECOM profile). Supported with
ACS355 drives only.
Note: The drive may limit the actual
number of the faults recorded.
947 R Array [64]
Unsigned16
Fault number.
950 R Unsigned16 Scaling of fault buffer
952 R/W Unsigned16 Number of faults occurred. Writing a zero
clears the value.
953 R Unsigned16
3)
Last alarm
954 R Unsigned16
3)
Second last alarm
955 R Unsigned16
3)
Third last alarm
956 R Unsigned16
3)
Fourth last alarm
957 R Unsigned16
3)
Fifth last alarm
958 R Unsigned16 Sixth last alarm (not supported)
959 R Unsigned16 Seventh last alarm (not supported)
960 R Unsigned16 Eighth last alarm (not supported)
963 R Unsigned16 Detected baud rate:
0 = 9.6 kbit/s
1 = 19.2 kbit/s
2 = 93.75 kbit/s
3 = 187.5 kbit/s
4 = 500 kbit/s
6 = 1.5 Mbit/s
7 = 3 Mbit/s
8 = 6 Mbit/s
9 = 12 Mbit/s
11 = 45.45 kbit/s
255 = Invalid baud rate
Par. no. R/W
1)
Data type Description
Subindex Contents
1 Active fault
Subindex Contents
See parameter 945.