Mounting
20 FSM4000 D184B140U02
4 Mounting
4.1 General information on installation
The following points must be observed for the installation:
• The flow direction must correspond to the identification if present.
• The maximum torque for all flange connections must be complied with.
• The devices must be installed without mechanical tension (torsion, bending).
• Install flange and wafer units with coplanar counter flanges and use only appropriate
gaskets.
• Use only gaskets made from a compatible material for the fluid and fluid temperature or use
only gasket material compatible with hygienic designs.
• Gaskets must not extend into the flow area since possible turbulence could influence the
device accuracy.
• The pipeline may not exert any unallowable forces or torques on the device.
• Do not remove the plugs in the cable connectors until you are ready to install the electrical
cable.
• Make sure the gaskets for the housing cover are seated properly. Carefully seal the cover.
Tighten the cover fittings.
• Install the separate transmitter at a largely vibration-free location.
• Do not expose the transmitter to direct sunlight. Provide appropriate sun protection as
necessary.
4.2 Supports for nominal diameters larger than DN 350
Notice - Potential damage to parts!
Improper support for the device may result in deformed housing and damage to internal
magnet coils.
Place the supports at the ed
.
Devices with a nominal diameter larger than DN 350 must be mounted with support on a
sufficiently strong foundation.
G00462
Fig. 10: Support for nominal diameters larger than DN 350