Electrical connections
D184B140U02 FSM4000 35
5.2 Connecting the flowmeter sensor
5.2.1 Connecting the signal and magnet coil cables
The flowmeter sensor is connected to the transmitter via the signal / magnet coil cables (part
no. D173D025U01 / D173D147U01). The coils of the flowmeter sensor are supplied with a field
voltage by the transmitter over terminals M1/M3. Connect the cables to the flowmeter sensor
according to the following drawing, using a screwdriver with proper size and width.
G00553
SE
SE
3A
3A
1S
2S
12 3
16
16
M1
M3
1
2
3
6
5
7
4
6
9
8
G00554
SE
SE
3A
3A
U- U+
12
3
16
16
M1
M3
1
2
3
6
5
7
4
6
9
8
Terminal box without preamplifier Terminal box with preamplifier
Fig. 32
1 red
2 blue
3 yellow
4 white
5 black
6 SE clamp
7 Signal cable
8 Grounding screw
9 Ma
g
net coil cable
1 red
2 blue
3 yellow
4 white
5 black
6 SE clamp
7 Signal cable
8 Grounding screw
9 Ma
g
net coil cable
Terminal designation Connection
1 + 2 Wires for the measuring signal
1S, 2S Shielding for signal wires
U+, U- Power supply for preamplifier via signal cable shielding
16 Cable for reference signal
3A Shielding for reference signal cable
3 Measuring ground (yellow)
M1 + M3 Connections for magnetic field excitation (black)
SE Outer cable shield