Commissioning
D184B140U02 FSM4000 53
Example of local address setting (DIP switch 8 = On)
G00564
123456789A
On
12
Fig. 50 Position of DIP switches
1 Transmitter plug-in module 2 DIP switch
Switches 1, 5, 7 = ON means: 1+16+64 = 81 Bus address 81
Switch 1 2 3 4 5 6 7 8 9 A
Status Unit address
Address
mode
no
function
no
function
Off 0 0 0 0 0 0 0 Bus
no
function
no
function
On 1 2 4 8 16 32 64 Local
no
function
no
function
Switch assignments
Switch Assignment
1 … 7 PROFIBUS address
8 Defines the addressing mode:
Off = Set address via bus (factory setting)
On = Set address via DIP switches nos. 1 ... 7