Parameterization
64 FSM4000 D184B140U02
Submenu/parameter Value range Comment
Unit Qmax
l/s; l/min; l/h; m
3
/s;
m
3
/min; m
3
/h; m
3
/d;
usgps; usgpm;
usgph; usmgd; igps;
igpm; igph; igpd;
bbl/s; bbl/m; bbl/h;
bbl/d; g/s; g/min, g/h;
kg/s;kg/min; kg/h;
kg/d; t/min; t/h; t/d;
lb/s; lb/min; lb/h; lb/d;
ml/s, ml/min
Prog. Unit/s
1)
Prog. Unit/min
1)
Prog. Unit/h
1)
Prog. Unit/d
1)
Select the unit for volume and mass flow. This unit refers
to Qmax DN, Qmax and the instantaneous status, if these
are displayed in engineering units.
For PROFIBUS PA, the following units are also displayed:
en ft
3
/s; ft
3
/min; ft
3
/h; ft
3
/d.
For PROFIBUS PA, the following units are not displayed:
Prog. unit and ml/s.
1)
kgal = Factory setting
l/s
Submenu
This menu does not appear for the PROFIBUS PA or
FOUNDATION fieldbus.
Prog. Unit
Unit name
Text entry Four character name for the user programmable unit.
kgal = Factory setting.
kgal
Unit factor
Numeric entry Reference factor for the user-defined units based on
liters; default value in kgal units (factory setting).
3785.1
Prog. Unit
Without density
With density
Unit for mass (with density) or volume (without density).
without density
Density
Numeric entry
Density range 0.1 ... -5 g/cm
3
. Mass flowrate for display
and totalization. The density is only considered when
mass flow units are and/or totalizer mass units are
selected.
1 g/cm
3
Submenu
System data
Submenu
Converter
Submenu
This menu does not appear with an excitation frequency
of 60 Hz or 70 Hz.
Data 50 Hz
Channel
View only
Adjustment value for Channel can be monitored for the
excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).
-123 µs
Zero
View only Adjustment value for Zero can be monitored for the
excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).
0 %
Span V
View only Adjustment value for Span Forward can be monitored for
the excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).
91 %
Span R
View only Adjustment value for Span Reverse can be monitored for
the excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).
-91 %