Parameterization
D184B140U02 FSM4000 87
Submenu/parameter Value range Comment
Submenu
Syst. Adjust
Start System Zero Manual
Autom. Calibration
Check zero, if necessary (when adapting an older
flowmeter sensor). Manual entry, e.g., when replacing the
transmitter.
0.0 %
System zero point Numerical entry Automatic adjustment: Valve must be closed, fluid in
flowmeter sensor must be at absolute standstill. Press
ENTER to perform the automatic adjustment. The limit for
the zero point is ± 10%. If the value is outside this limit, no
calibration is performed.
0.0 %
FSM4000 01/2010 Display only Display software version. 01.2010 specifies the date of
the release. C0.11 = Version level, for standard and
HART protocol models.
D699G004U01 C0.11
FSM4000 PA3.0 Display only For PROFIBUS PA software.
D699G004U02 C0.13
FSM4000 FF Display only For FOUNDATION Fieldbus communication software.
D699G004U03 C0.14