ABB i-bus
®
KNX
Commissioning
114 2CDC508134D0202 | FCA/S 1.x.x.1
Send object value
Options:
No, update only
On change
After request
After a change or request
No, update only: The object value is updated but not sent.
On change: The object value is sent when a change occurs.
After request: The object value is sent when a request occurs.
After a change or request: The object value is sent when a change or request occurs.
Data type 1-bit/byte
Options:
Bit
Byte
This parameter defines the data type of the communication object Status Control value.
1 bit: The following parameter appears:
Object value with control > 0
Options:
0
1
If the object value at control is greater than 0, a 1-bit telegram is sent using the value
defined here.
1-byte: The status of the control is sent via a 1-byte telegram.