Page #73 background image
ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 71
Enable communication object
"Request status values" 1 bit
Options:
No
Yes
Via this communication object, all status messages can be requested, provided that they have been
parameterized with the option After a change or request.
Yes: The 1-bit communication object Request status values is enabled.
Dependent parameter:
Request with object value
Options:
0
1
0 or 1
0: Sending status messages is requested with the value 0.
1: Sending status messages is requested with the value 1.
0 or 1: Sending status messages is requested with the values 0 or 1.
Note
If the option Yes has been selected for the parameter Enable communication object "Request status
values" 1-bit, the communication objects no. 4, 18, 28, 38 and 48 are sent immediately. For all other
status objects, e.g. for the fan, it is also possible to use parameters to set the time when each of them is
to be sent to the bus.