ABB i-bus
®
KNX
Commissioning
94 2CDC508134D0202 | FCA/S 1.x.x.1
Parameter window Enable output A...D Fan Coil Actuator, PWM
Operation mode output A and B
Options:
Individual
Valve drive, motor-driven (3-point)
This parameter determines whether the operation modes of outputs A and B can be parameterized
individually or whether the outputs are operated in operation mode Valve drive, motor-driven (3-point). The
outputs are linked to one another in pairs in this operation mode. Outputs A and B control the contacts
Open/Close of the valve drive for opening/closing the valve.
Individual: With this setting, the operation modes of outputs A and B are set individually from one
another.
Dependent parameters:
Output A
Output B
Options:
Disabled
Valve drive, thermoelectric (PWM)
This parameter defines the individual operation mode of the output.
Disabled: No operation mode selected.
Valve drive, thermoelectric (PWM): The parameter (window) and communication objects for the
operation mode Valve drive, thermoelectric (PWM) are enabled.
Valve drive, motor-driven (3-point): The parameter (window) and communication objects for the
operation mode Valve drive, motor-driven (3-point) are enabled.
Output A
Open
Output B
Close