ABB i-bus
®
KNX
Commissioning
178 2CDC508134D0202 | FCA/S 1.x.x.1
Cyclic sending
Options:
No
Yes
What is cyclic sending?
Cyclic transmission enables the communication object Switch to send automatically at a
fixed interval. If cyclic transmission is only carried out for a specific object value (ON or
OFF), this condition refers to the value of the communication object. It is therefore possible
in principle to start cyclic transmission by sending a value to the communication object
Switch. As this behavior is unwanted, the flags Write and Update of the communication
object are deleted in the preliminary setting, so that they cannot be changed via the bus. If
this functionality is required irrespectively, these flags should be set accordingly. When the
communication object Switch changes and after bus recovery (after the sending delay time
has elapsed), the communication object value is sent immediately on the bus, and the
sending cycle time restarts.
Selection Yes:
Dependent parameters:
Telegram is repeated
Options:
Every second
Every 2/3/5/10/30/60 seconds
Every 2/3/5/10/30/60 minutes
Every 2/3/5/10/12 hours
The sending cycle time describes the time used between two cyclically sent telegrams.
On object value
Options:
0
1
0 or 1
1: The communication object value is sent cyclically with 1.
0: The communication object value is sent cyclically with 0.
0 or 1: The communication object values 0 or 1 are sent cyclically.