182 2CDC508134D0202 | FCA/S 1.x.x.1
Example: Maximum dead time of the input signal for a detected edge:
After detection of an edge on the input, further edges are ignored for the maximum dead time T
D
.
Enable communication object
"Block" 1-bit
Options:
No
Yes
Yes: The 1-bit block communication object Block is enabled. This can be used to disable the input.
Notes
If the input is disabled and the option Send cyclically is set, the last state is still sent regardless of the
block. The option Block still blocks the physical input, sending continues internally.