ABB i-bus
®
KNX
Commissioning
70 2CDC508134D0202 | FCA/S 1.x.x.1
Rate of telegrams
Options:
Do not limit
1/2/3/5/10/20 telegram(s)/second
0.05/0.1/0.2/0.3/0.5 seconds/telegram
Using this parameter, the bus load generated by the device can be limited.
1/2/3/5/10/20 telegram(s)/second: X telegrams per second are sent.
0.05/0.1/0.2/0.3/0.5 seconds/telegram: A telegram is sent every x seconds.
Enable communication object
"In operation", 1 bit
Options:
No
Send value 0 cyclically
Send value 1 cyclically
The communication object In operation indicates that the device on the bus is working properly. This cyclic
telegram can be monitored by an external device.
Send value 0/value 1 cyclically: The value 0 or 1 is sent cyclically and the 1-bit communication object
In operation is enabled.
Dependent parameter:
Telegram is repeated
Options:
Every second
Every 2/3/5/10/30/60 seconds
Every 2/3/5/10/30/60 minutes
Every 2/3/5/10/12 hours
Note
After bus voltage recovery, the communication object sends its value after the set sending and
switching delay.