0: Forced operation is activated by a telegram with value 0.
1: Forced operation is activated by a telegram with value 1.
During forced operation the settings set in Automatic control are ignored. Automatic control is
updated after forced operation has been rescinded.
Forced operation remains active until:
the complementary set values are sent.
the assignment is changed;
the fan type is changed.
Forced operation is not deactivated by a download of the application, in which the fan type and
the respective group addresses are retained.
Forced operation is reset if an ETS reset has occurred.