ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 127
Forced operation on object value
Options:
0
1
0: Forced operation is activated by a telegram with value 0.
1: Forced operation is activated by a telegram with value 1.
Note
During forced operation the settings set in Automatic control are ignored. Automatic control is
updated after forced operation has been rescinded.
Important
Forced operation remains active until:
the complementary set values are sent.
the assignment is changed;
the fan type is changed.
Forced operation is not deactivated by a download of the application, in which the fan type and
the respective group addresses are retained.
Forced operation is reset if an ETS reset has occurred.