ABB i-bus
®
KNX
Commissioning
130 2CDC508134D0202 | FCA/S 1.x.x.1
What is current fan speed?
The Current fan speed is the speed at which the fan is actually operating.
What is required fan speed?
The Required fan speed is the fan speed which has to be reached, e.g. when the transition
and dwell times have elapsed.
Note
The limitations are included in this observation, i.e. if a limitation allows only fan speed 2,
the fan is operating at fan speed 2, and, for example, a telegram to switch up is received,
the required fan speed remains at 2, as fan speed 3 cannot be reached due to the
limitation.
Send object values
Options:
No, update only
On change
After request
After a change or request
No, update only: The status is updated but not sent.
On change: The status is sent when a change occurs.
After request: The status is sent when a request occurs.
After a change or request: The status is sent on a change or a request.