ABB i-bus
®
KNX
Commissioning
180 2CDC508134D0202 | FCA/S 1.x.x.1
3.2.4.2.2 Parameter Distinction between long and short operation Yes
If the option Yes has been selected with the parameter Distinction between long and short operation, the
following parameters appear in Parameter window a: Switch sensor, p. 171:
Short operation -> Event 0
Long operation -> Event 1
<−−− NOTE
Input on operation
Options:
open
Closed
Open: The input is opened with actuation.
Closed: The input is closed with actuation.
If a normally open contact is connected to the input, the option Closed should be selected; on a
normally closed contact the option Open should be selected.
Long operation after …
Options:
0.6/0.8 s
1/1.2/1.5 s
2/3/4/5/6/7/8/9/10 s
Here the time period T
L
, after which an operation is considered a “long” operation, is defined.
Note
The remaining parameter descriptions can be found in Parameter Distinction between long
and short operation No, p. 173.