Note/IllustrationAction
xx2100000832
Remove the attachment screws on the
door.
5
Push the HMI signal connector into the
cabinet.
6
Take out the HMI signal connector.7
Refitting the HMI signal connector
Refitting the HMI signal connector
Note/IllustrationAction
DANGER
Before doing any work inside the cabinet,
disconnect the mains power. For more
information, see Electrical safety on
page 29.
1
Location of wrist strap button:
ELECTROSTATIC DISCHARGE
(ESD)
The unit is sensitive to ESD. Before
handling the unit read the safety inform-
ation in section The unit is sensitive to
ESD on page 45.
2
xx2300001842
Continues on next page
298 Product manual - OmniCore V400XT
3HAC081697-001 Revision: A
© Copyright 2022-2023 ABB. All rights reserved.
5 Repair
5.3.3 Replacing the HMI signal (FlexPendant) connector
Continued