NoteAction
Make sure that the safety cable is connected
properly on both ends.
If the connection seems OK, proceed
with step 5.
If there is a problem with the connection,
proceed with step 11.
Check the safety cable connection:
X17.
10
Make sure that the safety cable is connected
properly on both ends.
If the connection seems OK, the fault has
been fixed. Proceed with step 1.
If there is a problem with the connection,
replace the safety related cables. See
12.
Restore the communication of the
safety cable between the modules
by reconnecting the cable X17.
11
If the connection seems OK, the fault has
been fixed. Proceed with step 1.
If the fault remains, see Troubleshooting
the power unit on page 381.
Replace the safety cable: X17.12
Product manual - OmniCore V400XT 373
3HAC081697-001 Revision: A
© Copyright 2022-2023 ABB. All rights reserved.
7 Troubleshooting
7.3.3 Troubleshooting the drive unit
Continued