20 PCS100 AVC-20 User Manual
3.4 PCS100 AVC-20 Model Range
400 V and 415 V Application Voltage
Rated apparent
power
[kVA]
Rated real power [kW]
Fault Capacity [kA
]
Losses [kW] (Typical)
Efficiency [%] (Typical)
Airflow [m
3
/min]
Frame Size
Type Code
To complete the Type Code:
Place R for right
termination side or L for
left termination side
instead of x
400 V, 415 V
Utility Voltage
±15%
regulation
±20%
regulation
250
250
187
15
1.8
99.3
18
1B
PCS100-28-400-0B5-20
500
500
375
15
4.7
99.1
18
1B
PCS100-28-400-01B-20
1000
1000
750
31.5
8.6
99.1
36
2B
PCS100-28-400-02B-20-x
1500
1500
1125
31.5
13.2
99.1
54
3B
PCS100-28-400-03B-20-x
2000
2000
1500
40
14.5
99.3
72
4B
PCS100-28-400-04B-20-x
2500
2500
1875
50
19.1
99.2
90
5B
PCS100-28-400-05B-20-x
3000
3000
2250
63
24.3
99.2
108
6B
PCS100-28-400-06B-20-x
380 V Application Voltage
Rated apparent
power
kVA
Rated real power kW
Fault Capacity [kA]
Losses [kW]
(Typical)
Efficiency [%] (Typical)
Airflow [m3/min]
Frame Size
Type Code
To complete the Type Code:
Place R for right
termination side
or L for left termination
side
instead of x
380 V
Utility Voltage
±15%
regulation
±20%
regulation
237
237
177
15
1.8
99.3
18
1B
PCS100-28-400-0B5-20
475
475
356
15
4.7
99.1
18
1B
PCS100-28-400-01B-20
950
950
712
31.5
8.6
99.1
36
2B
PCS100-28-400-02B-20-x
1425
1425
1068
31.5
13.2
99.1
54
3B
PCS100-28-400-03B-20-x
1900
1900
1425
40
14.5
99.3
72
4B
PCS100-28-400-04B-20-x
2375
2375
1781
50
19.1
99.2
90
5B
PCS100-28-400-05B-20-x
2850
2850
2137
63
24.3
99.2
108
6B
PCS100-28-400-06B-20-x
Table 3-2: PCS100 AVC-20 model range

Table of Contents

Related product manuals