EasyManua.ls Logo

ABB PCS100 AVC-20 - PCS100 AVC-20 Model Range

ABB PCS100 AVC-20
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20 PCS100 AVC-20 User Manual
3.4 PCS100 AVC-20 Model Range
400 V and 415 V Application Voltage
Rated apparent
power
[kVA]
Rated real power [kW]
Fault Capacity [kA
]
Losses [kW] (Typical)
Efficiency [%] (Typical)
Airflow [m
3
/min]
Frame Size
Type Code
To complete the Type Code:
Place R for right
termination side or L for
left termination side
instead of x
400 V, 415 V
Utility Voltage
±15%
regulation
±20%
regulation
250
250
187
15
1.8
99.3
18
1B
PCS100-28-400-0B5-20
500
500
375
15
4.7
99.1
18
1B
PCS100-28-400-01B-20
1000
1000
750
31.5
8.6
99.1
36
2B
PCS100-28-400-02B-20-x
1500
1500
1125
31.5
13.2
99.1
54
3B
PCS100-28-400-03B-20-x
2000
2000
1500
40
14.5
99.3
72
4B
PCS100-28-400-04B-20-x
2500
2500
1875
50
19.1
99.2
90
5B
PCS100-28-400-05B-20-x
3000
3000
2250
63
24.3
99.2
108
6B
PCS100-28-400-06B-20-x
380 V Application Voltage
Rated apparent
power
kVA
Rated real power kW
Fault Capacity [kA]
Losses [kW]
(Typical)
Efficiency [%] (Typical)
Airflow [m3/min]
Frame Size
Type Code
To complete the Type Code:
Place R for right
termination side
or L for left termination
side
instead of x
380 V
Utility Voltage
±15%
regulation
±20%
regulation
237
237
177
15
1.8
99.3
18
1B
PCS100-28-400-0B5-20
475
475
356
15
4.7
99.1
18
1B
PCS100-28-400-01B-20
950
950
712
31.5
8.6
99.1
36
2B
PCS100-28-400-02B-20-x
1425
1425
1068
31.5
13.2
99.1
54
3B
PCS100-28-400-03B-20-x
1900
1900
1425
40
14.5
99.3
72
4B
PCS100-28-400-04B-20-x
2375
2375
1781
50
19.1
99.2
90
5B
PCS100-28-400-05B-20-x
2850
2850
2137
63
24.3
99.2
108
6B
PCS100-28-400-06B-20-x
Table 3-2: PCS100 AVC-20 model range

Table of Contents