EasyManua.ls Logo

ABB PCS100 AVC-20 - Description of Power Quality Event Notification

ABB PCS100 AVC-20
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PCS100 AVC-20 User Manual 91
10.4.2.5 Description of Power Quality Event Notification
Below is an example of a typical email sent to notify the customer of a power quality event.
From: AVC-40@nz.abb.com
Sent: Tuesday, 22 September 2015 10:52 a.m.
To: Customer <customer@factory.com>
Subject: Power Quality Event 12345678
Customer:
ABB NZ
Site Name:
Napier
Plant Name:
Site 1
Site Information
Note:
AVC connected to Production Line 75
Note:
Feeder 12 O/G
Product type:
PCS100 AVC-20
Model:
Product Rated voltage:
480.00V
Product Information
Product Rated Power:
1000kVA
Date
2015-09-21
Date and Time
Time
10:49:38.27
Input voltage V1
80%
Input voltage V2
82%
Utility sag at input to PCS100 AVC-20
Input voltage V3
87%
Output voltage V1
100%
Output voltage V2
100%
PCS100 AVC-20 sag correction
Output voltage V3
99%
Duration
200 ms
Sag duration
Event type
sag
Type of PQ event
System Status
running
Status of PCS100 AVC-20

Table of Contents