PCS100 AVC-20 User Manual 89
10.4 Email Connectivity
PCS100 AVC-20 is configurable for sending e-mail notifications in case of power quality event or systems internal
event as faults and warnings.
Automatic sending of the service logs via e-mail to ABB Service can also be enabled.
Figure 10-10 highlights the Email Menu Page which shows the parameters that the operator needs to set up as
described in Sections 10.4.1 10.4.4
Figure 10-10: Email Menu Page
10.4.1 Setting up Email Server
The Email Notification Service (ENS) requires an SMTP server to send its emails out that is accessible on the local
network and does not support authentication. The GDM needs to be configured for the local network refer to
Sections 10.2.1 - 10.2.2 for configuration instructions.
A minimum of operator access is required to configure the ENS via the GDM Menu.
The email server should be set up as described below:
From the GDM menu select 7 GDM Services and then select 77 Email Service
Select 770 SMTP Server and enter the IP address of the SMTP server.
Select 773 From Address and enter an address that the email server will accept
Enter the Customer notes as required using menu “774 and 775 Customer note 1 and 2”. Here the
customer is free to enter additional information.
Note: The Email server is not contacted until an email is sent either by an event trigger or the force
email function.