88 PCS100 AVC-20 User Manual
Address
Name
Access
Type
Raw Value & Scaling
1002
Start
Command
Read/Write
16-bit,
Enum
0 = No Action
1 Start
1004
Stop
Command
Read/Write
16-bit,
Enum
0 = No Action
1 = Stop
1006
Output
Voltage
Setpoint
Read/Write
16-bit,
Signed
Voltage (line-to-line RMS volts) = raw value
x rated voltage / 8192
1007
Test Register
Read/Write
16-bit,
Signed
Dummy read / write register for testing
Table 10-1: PCS100 AVC-20 Modbus TCP User Parameters
10.3.4 Modbus TCP Error Codes
The following error codes may be returned by the Modbus TCP server.
Code
Name
Description
1
Illegal Function
Function code received in the query is not supported by this
Modbus TCP server or the query is badly formatted.
2
Illegal Data Address
The data address received in the query is not a valid address in
the Modbus TCP server. Specifically, the combination of address
and number of registers is not valid.
Register not known by the PCS100 AVC-20
Register is not in Modbus TCP configuration table
Not all registers of a single parameter accessed
Register / length mismatch
3
Illegal Data Value
The value received in the query is not an allowable value for this
register or the implied length is invalid.
Value out of range for parameter
Number of registers requested exceeds max.
4
Slave Device Failure
An unrecoverable error occurred while server attempted to
perform requested action.
Read/Write access violation
GDM hardware issues
Insufficient access privileges
6
Slave device Busy
The Modbus TCP server is unable to process this command at
present. Retry this command again later.
GDM VCAN server busy or unavailable
Table 10-2: PCS100 AVC-20 Modbus TCP error codes