88 PCS100 AVC-20 User Manual
Voltage (line-to-line RMS volts) = raw value
x rated voltage / 8192
Dummy read / write register for testing
Table 10-1: PCS100 AVC-20 Modbus TCP User Parameters
10.3.4 Modbus TCP Error Codes
The following error codes may be returned by the Modbus TCP server.
Function code received in the query is not supported by this
Modbus TCP server or the query is badly formatted.
The data address received in the query is not a valid address in
the Modbus TCP server. Specifically, the combination of address
and number of registers is not valid.
– Register not known by the PCS100 AVC-20
– Register is not in Modbus TCP configuration table
– Not all registers of a single parameter accessed
– Register / length mismatch
The value received in the query is not an allowable value for this
register or the implied length is invalid.
– Value out of range for parameter
– Number of registers requested exceeds max.
An unrecoverable error occurred while server attempted to
perform requested action.
– Read/Write access violation
– GDM hardware issues
– Insufficient access privileges
The Modbus TCP server is unable to process this command at
present. Retry this command again later.
– GDM VCAN server busy or unavailable
Table 10-2: PCS100 AVC-20 Modbus TCP error codes