PCS100 AVC-20 User Manual 87
Address
Name
Access
Type
Raw Value & Scaling
16
Frequency
Read Only
16-bit,
Signed
Frequency (Hz) = raw value x rated
frequency / 8192
e.g., raw value = 8192
rated frequency = 60Hz
Frequency = 60.0Hz
17
Active Event
Code
Read Only
16-bit,
Signed
See Table 9-2Event code 0 indicates there
are no active events (no warning/fault).
18
Auto
Increment
Register
Read Only
16-bit,
Enum
Read = Register automatically increments
by 1 every time this is read
26
Product Code
Read Only
16-bit
unsigned
7300=AVC
27
SCM Fault
Code
Read Only
16-bit
unsigned
System Configuration Module state (fault
code)
28
PQ sag count
Read Only
16-bit
unsigned
0%-10%
29
PQ sag count
Read Only
16-bit
unsigned
10%-20%
30
PQ sag count
Read Only
16-bit
unsigned
20%-30%
31
PQ sag count
Read Only
16-bit
unsigned
30%-40%
32
PQ sag count
Read Only
16-bit
unsigned
40%-50%
33
PQ sag count
Read Only
16-bit
unsigned
50%-60%
34
PQ sag count
Read Only
16-bit
unsigned
60%-70%
35
PQ sag count
Read Only
16-bit
unsigned
70%-80%
36
PQ sag count
Read Only
16-bit
unsigned
80%-90%
37
PQ surge
count
Read Only
16-bit
unsigned
>110%
38
Output
Apparent
Power
Read Only
16-bit
signed
Per-unit. Base Power
= 3 * Rated Voltage (register 4) * Rated
Current (register 6)
39
Output Real
Power
Read Only
16-bit
signed
100
Time and
Date
Read/Write
32-bit
unsigned
Unix (Epoch) Time Number of seconds
since 01/01/1970.
Note If write error, enable with menu 731
Date Write Enable
1000
Reset
Command
Read/Write
16-bit,
Enum
0 = No Action
1 = Reset