60 PCS100 AVC-20 User Manual
Displays the SCM (System Configuration Module) software revision
Displays the CGI software revision
Displays the Modbus software revision
Displays the NTP (Network Time Protocol) software revision
Displays the Email software revision
Table 8-5: Menu 3 Product Revision Parameters
8.3.6 Menu 6 References
8.3.6.1 Submenu 60 V Setpoint
The submenu contains parameters for configuring for the output voltage setpoint
Note: This menu is only visible with Tech login
Sets the target output voltage of PCS100 AVC-20
Nameplate rating of PCS100 AVC-20
Set to nominal supply voltage ± 10% (RMS)
Typically, this parameter is set to the same value as 13 Supply Voltage. If set too close
to 15 Sag Threshold or 16 Surge Threshold spurious sag/surge events may be
recorded in the event log.
Sets the source of output voltage setting
Manual / AIN1 / AIN2 / Modbus
For settings other than Manual the Extended I/O board is required.
For an AVC without an Extended IO board only manual adjustment of the AVC output
voltage is available.
Table 8-6: Menu 6 Reference Parameters
Note:
Additional parameters in this submenu are related to optional Extended I/O board and are not used
with standard PCS100 AVC-20 operation and thereby not described in this document. Complete
parameter descriptions are shown in separate document related to Extended I/O board.