PCS100 AVC-20 User Manual 23
4.7 Standards and Certifications
Declaration of Conformity – This product conforms to the following standards.
Electromagnetic compatibility
Emissions: CISPR 11 Class A Group 1
Immunity: IEC 61000-6-2
Operating temperature range
Above 40 °C, derate at 2% load per °C to a maximum of 50 °C
< 1000 m without derating
Capacity derating with altitude
1% every 100 m above 1000 m
2000 m maximum
Storage temperature range
Must be kept dry at all times including transportation and
storage. Protect against contact with rain or other water or
liquids and do not store in damp or humid conditions.