64 PCS100 AVC-20 User Manual
Parameter
779 System_Event
Function:
Allows operator to configure and test the System event email notifications.
Setting Up:
7790 Email Address: Destination email address for the system event email
notification to be sent to.
7791 Trigger Type: Gives the operator the option to choose the event that will
trigger an email. The options include:
Trigger notification on fault
Trigger notification on warning
Trigger notification on Power Quality
7792 Force Email: Allows user to test the System event email notification service
when set to true. An email will be sent out using the email server
settings and the email address entered in 7790. Allow up to a
couple minutes for the email to be sent.
7793 Enable: When set to true, this enables PQ event email notifications to be
sent to the operator.
Parameter
77A Service Log
Function
Creates a service log email that is sent out on the 1
st
of every month. This is setup in
the factory.
8.3.8 Menu Graphic display
8.3.8.1 Submenu A00 Display
A00 Display
The menu contains parameters to setup the graphic display module
Name:
A31 GDM Control Enable
Function:
Enables or disables the local Start, Stop, Reset control.
Range:
True / False
Factory Setting:
True
Access:
Operator
Name:
A62 Screen Saver Time
Function:
Sets the time for the screen saver to activate.
Range:
0 min to 999 min
Factory Setting:
15 min
Access:
Operator
Name:
A63 SSH Port Enable
Function:
Enables SSH access.
Range:
True / False
Factory Setting:
False
Access:
Operator
Name:
A64 Firmware Upload Enable
Function:
Enables firmware uploads
Range:
True / False
Factory Setting:
False
Access:
Operator
Table 8-8: Submenu A00 Display Parameters