EasyManua.ls Logo

ABB PCS100 AVC-20 - Stop - Enable Switch

ABB PCS100 AVC-20
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
98 PCS100 AVC-20 User Manual
11.3 Stop Enable Switch
A Stop-Enable switch is mounted inside of the Master Controller Enclosure as a failsafe device.
In case of any user interface display or remote-control failure this switch can be used to stop the PCS100 AVC-20
operating and put it into BYPASS mode by setting to STOP. This will inhibit PCS100 AVC-20 from starting.
This switch is wired in series with the remote inhibit input above.
Returning this switch to Enable will enable the controller but not start it. A local or remote start is needed to bring
the system out of BYPASS.

Table of Contents

Related product manuals