24 PCS100 AVC-20 User Manual
4.9 Enclosure
Enclosure rating
IP20
Material
Electro-galvanized steel
Panel thickness
Side and rear
Door
1.5 mm
2 mm
Finish
Standard epoxy-polyester powder coating textured finish.
Color
RAL7035
Enclosure access
Hinged doors with key lock
4.10 Service
MTTR
30 min typical by module exchange
Diagnostics
Non-volatile event & service log
Remote monitoring
E-mail
4.11 Power Quality Event Monitor
Events recorded
Voltage Sag (RMS)
Voltage Surge (RMS)
Event detection
Input Voltage
Sag threshold
90% of Utility voltage default setting (user adjustable)
Surge threshold
110% of Utility voltage default setting (user adjustable)
Accuracy
Voltage: ± 2%
Duration: 10 ms
Remote monitoring
Web Server
Remote notification
E-mail
4.12 User Interface
User interface
10.1” color touch panel
Touch panel
Full parameter control
Control inputs
Start / Stop / Reset digital inputs
Control outputs
Running, Warning and Fault relays
Communication
Ethernet
Modbus TCP
E-mail