PCS100 AVC-20 User Manual 93
10.4.3.3 Description of System Event Notification
Below is an example of a typical email sent to notify the customer of a system event.
From: AVC-40@nz.abb.com
Sent: Saturday, 19 September 2015 4:31 p.m.
To: Customer <customer@factory.com>
Subject: System Event 60001234 fault
surSite Information
Product Information
Date and Time
Highlights
Date
Time
Origin
Event
Cod
e
Description
2015-09-18
16:30:22.00
scm
scm info
1002
scm power up
2015-09-18
16:30:19.00
scm
scm info
1001
scm power supply fail
2015-09-18
16:30:19.00
inverter 1
scm info
1008
presence message seen
2015-09-18
16:30:13.91
system
fault
70
inverter lost
2015-09-18
16:30:13.34
inverter 1
fault
2
desat
2015-09-18
16:30:13.25
inverter 1
warning
4
lvdc psu voltage low
2015-09-18
16:24:39.61
sag end
running ,200 ms, 80%, 75%, 80%, 100%, 100%,
100%
2015-09-18
16:24:39.61
sag end
running,200ms,79%,76%,80%,100%,100%,100%
Note: The table lists the System and PQ events. The event that triggers the email is highlighted in bold text.
Customer:
ABB NZ
Site Name:
Napier
Plant Name:
Site 1
Note:
AVC connected to Production Line 75
Note:
Feeder 12 O/G
Product type:
PCS100 AVC-20
Model:
Product Rated voltage:
480.00V
Product Rated Power:
1000kVA
Date
2015-09-18
Time
16:30:13.34
Event Code:
2
Event Description:
desat
Status of PCS100 AVC-20
Duration of Voltage sag
Utility sag at input to PCS100 AVC-20
PCS100 AVC-20
sag correction

Table of Contents