The rectifier or inverter lost
communication with master
module.
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
Two consecutive frames
have been lost from the
Streaming Data Interface.
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
The Streaming Data
Interface frame loss
exceeds the threshold.
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
Master lost
communications with
critical TCPM (PC).
Check the PC connections.
Master lost
communications with
critical GDM.
Check the GDM connections.
A module has been
replaced. The replacement’s
number was not
recognized.
If a module has been replaced
check the module ID number is
set to the same as the
replaced module.
Number of rectifier and
inverter modules is
unequal.
- Ensure module IDs are set
correctly
- Call service agent
There are sustainable
communication errors
between the module display
board and Digital Signal
Processor Engine (DSPE).
Ensure the module display
board is firmly plugged into
interface board.
There were unsustainable
communication errors
between the module display
board and the Module DSPE
(Digital Signal Processor
Engine).
Ensure the module display
board is plugged firmly into
interface board.
The input voltage is below
the operation threshold.
Note: This is normal when
the input voltage is
removed or applied.
Check utility voltage is within
the thresholds.
Utility open source
detected. Input has been
switched off.
Commissioning test mode
has been activated.
Setting: 915 Relay Test
Modes
When the test has been
completed switch off the test
mode