FEM630 | ELECTROMAGNETIC FLOWMETER | OI/FEM630-EN REV. A
Menu / parameter
Device Setup / ...Transmitter
...Units
Selection of submenu ‘...Units’ using .
Damping
Select the damping.

change. It affects the instantaneous value in the display and at the current output.

Damping On/Off Switches the damping on or off.
Density Fixed Value
If the flow count and display are performed using mass flow units, a fixed density value must be included in the

...Cut Off
Selection of submenu ‘...Cut Off’ using .

Entry of the measuring point tag for the transmitter.


Enter the tag number for the transmitter.

Plant Data Sync.
Tx -> Sens
The settings are redundantly saved in two data modules. One of them is the SensorMemory, the other is the
transmitter motherboard (backplane).
By selecting ‘Tx -> Sens’, location-specific settings such as measuring range or damping are replicated from
the transmitter motherboard (backplane) to the SensorMemory.
Sens -> Tx
By selecting ‘Sens -> Tx’, location-specific settings such as measuring range or damping are replicated from
the SensorMemory to the transmitter motherboard (backplane).
Device Reset For service purposes only. Restart the device without having to switch the power supply on and off.
Restore Factory Def. All user-accessible parameters will be reset to the factory default settings.
...Feature Settings
Selection of submenu ‘...Feature Settings’ using .

 .
Noise Reduction
Activates the filter technology for noise reduction.


Default setting: Off
...Piston Pump
Enables improved measurement performance, especially in piston pump applications.
Filter On/Off: On/Off
Filter length: 3 to 30 sec
Strokes per minute: Indicates the piston pump strokes per minute
8 ...Operation
...Parameter descriptions