ProcessMaster FEP610, HygienicMaster FEH610 | OI/FEP610/FEH610-EN Rev. B 69
Error no. /
Range
Error text Current output Digital output Pulse output LCD display Error maskable?
C078.004 /
Config.
Flowrate to zero.
Check digital in terminals.
4 mA (0 % flow) Current value - no
change.
0 Hz 0 % Menu "...Group
Masking".
C076.006 /
Config.
All totalizer stopp.
Check digital in terminals.
Current value - no
change.
Current value - no
change.
Current value -
no change.
Current value -
no change.
C074.007 /
Config.
Totalizer reset.
Reset of one or more
Totalizers.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Menu "...Group
Masking".
C072.003 /
Config.
Simulation is on Simulated
values.
Switch off Simulation Mode.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Current value - no
change.
C070.027 /
Config.
An alarm is simulated.
Switch off alarm simulation.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Current value - no
change.
S065.044 /
Operation
Inhouse temp. alarm.
Reduce ambient
temperature.
Current value - no
change.
No response No response Current value - no
change.
S064.041 /
Operation
EPD alarm.
Secure pipe is completely
filled.
Alarm - as
configured in
menu "Curr. at
EPD Alarm".
Alarm if DO is
configured as
"Logic / Alarm
Signal / EPD".
0 0 % Menu "...Group
Masking".
S062.039 /
Operation
Sensor temp. limits alarm.
Change limits or change fluid
temperature.
Current value - no
change.
No response Current value - no
change.
Current value - no
change.
Menu "...Group
Masking".
S052.017 /
Operation
Curr.Out 31 / 32 is
saturated.
CO process value out of
range. Adapt Qmax.
Alarm - as
configured in
menu "Curr.Out >
20.5mA".
Current value - no
change.
Current value - no
change.
Current value - no
change.
Menu "...Group
Masking".
S047.016 /
Operation
Pulse output is cut off.
Wrong config. Check pulse
out configuration.
Current value - no
change.
Current value - no
change.
Maximum possible
pulse rate
Current value - no
change.
Menu "...Group
Masking".
S046.001 /
Operation
Mass flowrate exceeds
limits.
Check flowrate and alarm
limits.
Current value - no
change.
Alarm if DO is
configured as "Qm
Massflow Max" or
"Qm Massflow
Min".
Current value - no
change.
Current value - no
change.
Menu "...Group
Masking".
S044.002 /
Operation
Volume flowrate exceeds
limits.
Check flowrate and alarm
limits.
Current value - no
change.
Alarm if DO is
configured as "Qv
Volumeflow Max"
or "Qv Volumeflow
Min".
Current value - no
change.
Current value - no
change.
Menu "...Group
Masking".
S041.034 /
Electronics
DC feedback regulation.
Check conditions of
application. Call service.
4 mA (0 % flow) No response. 0 Hz 0 % Menu "...Group
Masking".
S040.031 /
Electronics
Coil impedance alarm.
Call service.
Current value - no
change.
No response. Current value - no
change.
Current value - no
change.
Menu "...Group
Masking".

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ProcessMaster FEP611 and is the answer not in the manual?

ABB ProcessMaster FEP611 Specifications

General IconGeneral
BrandABB
ModelProcessMaster FEP611
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals