Variable Group/
Channel 2
(R, W, P)
Setting range Default
setting
Custo-
mer s
setting
Checksum, SGR 1 2S81 0...8388607 10922
Checksum, SGR 2 2S82 0...8388607 10922
Checksum, SGR 3 2S83 0...8388607 10922
Checksum, SGR 4 2S84 0...8388607 5461
Checksum, SGR 5 2S85 0...8388607 5461
Checksum, SGR 6 2S86 0...8388607 0
Checksum, SGR 7 2S87 0...8388607 0
Checksum, SGR 8 2S88 0...8388607 0
Checksum, SGL 1 2S91 0...8388607 0
Checksum, SGL 2 2S92 0...8388607 0
Checksum, SGL 3 2S93 0...8388607 0
Checksum, SGL 4 2S94 0...8388607 0
Checksum, SGL 5 2S95 0...8388607 0
Checksum, SGL 6 2S96 0...8388607 0
Checksum, SGL 7 2S97 0...8388607 0
Checksum, SGL 8 2S98 0...8388607 0
Table 8.-3 Control parameters
Description Parameter
(channel 0)
Setting range Default setting Customers
setting
Rated frequency V104 50 or 60 Hz 60 Hz
Time setting range for
demand values in
minutes
V105 0...999 min 10 min
Non-volatile memory
settings
V106 0...31 31
Time setting for disabling
new trip targets on the
LCD
V108 0...999 min 60 min
Trip-circuit supervision V113 0 = not in use
1 = in use
0
Remote control of settings V150 0 = setting
group 1
1 = setting
group 2
0
Unit address of the relay V200 1...254 1
Data transfer rate (SPA),
kbps
V201 9.6/4.8 9.6
Rear communication
protocol
V203 0 = SPA
1 = IEC_103
2 = Modbus
RTU
3 = Modbus
ASCII
0