171
Description Parameter
(channel 0)
Setting range Default setting Customer’s
setting
Connection type V204 0 = loop
1 = star
0
Line-idle state V205 0 = light off
1 = light on
0
Optional communication
module
V206 0 = not in use
1 = in use
0
Table 8.-4 Parameters for the disturbance recorder
Description Parameter
(channel 0)
Setting range Default setting Customer’s
setting
Sampling rate M15 800/960 Hz
400/480 Hz
50/60 Hz
800 Hz
Station identification/unit
number
M18 0...9999 0
Name of the feeder M20 Max 16
characters
- ABB -
Analog channel
conversion factor and unit
for I
a
,I
b
and I
c
M80, M81, M82 Factor
0...65535, unit
(A, kA), e.g. 10,
kA
00001, CT
Analog channel
conversion factor and unit
for the ground-fault
current
M83 Factor
0...65535, unit
(A, kA), e.g. 10,
kA
00001, CT
Internal trigger signals'
checksum
V236 0...16383 682
Internal trigger signal's
edge
V237 0...16383 0
Checksum of internal
signal storing mask
V238 0...16383 751
Post-triggering recording
length
V240 0...100% 50 %
External trigger signal's
checksum
V241 0...31 0
External trigger signal's
edge
V242 0...31 0
Checksum of external
signal storing mask
V243 0...31 0
Table 8.-5 Auto-reclose parameters
Description Parameter
(channel 0)
Value Default setting Customer’s
setting
CB Closing time V121 0.1...10 s 0.2 s
Pickup delay of element
51P
V122 0...300 s 300 s
Pickup delay of element
51N
V123 0...300 s 300 s
Reclaim time V124 3...300 s 10 s
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610REF610
1MRS755535