EasyManua.ls Logo

ABB REL650 - Page 204

ABB REL650
516 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
have instantaneous function. The overcurrent protection of IED A1 must have a delayed
function. The sequence of events during the fault can be described using a time axis, see
figure 95.
A1 B1
Feeder
Time axis
t=0 t=t
1
t=t
2
t=t
3
The fault
occurs
Protection
B1 trips
Breaker at
B1 opens
Protection
A1 resets
ANSI10000279-1-en.vsd
51
51
ANSI10000279 V1 EN
Figure 95: Sequence of events during fault
where:
t=0 is when the fault occurs.
t=t1 is when the trip signal from the overcurrent protection at IED B1 is sent to the
circuit breaker. The operation time of this protection is
t1, t=t2 is when the circuit breaker at IED B1 opens. The circuit breaker opening time
is t2 - t1.
t=t3 is when the overcurrent protection at IED A1 resets. The protection resetting
time is t3 - t2.
To ensure that the overcurrent protection at IED A1, is selective to the overcurrent
protection at IED B1, the minimum time difference must be larger than the time t
3
. There
are uncertainties in the values of protection operation time, breaker opening time and
protection resetting time. Therefore a safety margin has to be included. With normal
values the needed time difference can be calculated according to equation
110.
40 100 40 40 220t ms ms ms ms msD ³ + + + =
EQUATION1266 V1 EN (Equation 115)
where it is considered that:
Section 7 1MRK 506 334-UUS A
Current protection
198
Application manual

Table of Contents

Other manuals for ABB REL650

Related product manuals