EasyManua.ls Logo

ABB REL650 - Page 62

ABB REL650
516 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
X1 ≥ 1.1 · X1 (Zone2) = 1.1 · 44.2 = 48.5 Ω
4.2. Set X0 to 140 Ω
X0 ≥ 1.1 · X0 (Zone2) = 138.9 Ω
5. Set the fault resistance reach (phase-phase)
5.1. Set RFltFwdPP to 70 Ω
5.2. Set RFltRevPP to 70 Ω
The setting RFltFwdPP, RFltRevPP, RFltFwdPG and RFltRevPG shall cover zone
2 both for phase-to-phase short circuits and three-phase short circuits.
RFltFwdPP ≥ 1.1 · RFPP (Zone2) = 1.1 · 44 = 48.4 Ω
It shall also be clarified that zone 2 is covered also for three-phase short circuits
where the phase selection has a phase shift of 30º and an amplitude increase of
2 3/
. The characteristic are shown in figure 11:
30
Phase-to-phase fault Three-phase-fault
0.
X1
60
4/ 3 X1
ANSI10000188_en_1.vsd
0.5 RFltRevPP
0.5 RFltFwdPP
0.5 RFltFwdPP
=
2
3
K
ANSI10000188 V1 EN
Figure 11: Phase selection impedance characteristic for two phase and three
phase short circuits
The figure shows that 0.5 · RFltFwdPP is larger than zone 2 maximum reach.
This gives:
44
0.5 cos(81.9 ) 28.8 57.6
2
RFltFwdPP 48 RFltFwdPP× ³ × + = Þ ³ W
o
GUID-BA41A96A-8C76-4BD2-A9C7-C485F8BB5021-ANSI V1 EN (Equation 18)
6. Set the fault resistance reach (phase-ground)
6.1. Set RFltFwdPG to 110 Ω
6.2. Set RFltRevPG to 110 Ω
RFltFwdPG≥ 1.1 · RFPE (Zone 2) = 1.1 · 100 = 110 Ω
Section 3 1MRK 506 334-UUS A
REL650 setting examples
56
Application manual

Table of Contents

Other manuals for ABB REL650

Related product manuals