6.4 Changing protection relay functionality
6.4.1 Defining the setting group
6.4.1.1 Activating a setting group
Protection relay settings are planned in advance for different operation conditions by
calculating setting values to different setting groups. The active setting group can be
changed by the protection relay application or manually from the menu.
1.
Select Main menu/Settings/Setting group/Active group and press
.
Section 6 1MAC054853-MB B
Operating procedures
102 615 series ANSI
Operation Manual