A071154 V3 EN
Figure 96: Entering IED blocked or IED test and blocked mode
2.
Select the test mode status with or . Press to confirm the selection.
If the IED blocked or IED test and blocked mode is not cancelled, it
remains on and the Pickup and/or Normal LEDs remain flashing.
8.6 ABB Product Data Registration
The ABB Product Data Registration feature traces composition changes in the protection
relay's SW or HW. Traceability allows better support and maintenance possibilities.
After a composition change, an LCT indication is seen on the LHMI at the protection relay
startup. The PCM600 reads the changed data from the protection relay. Therefore a
connection to the protection relay must be established first. Composition data can be read
with PCM600 by enabling LCT during PCM600 installation and activating collection in
PCM600 from 'Lifecycle Handling' menu. For detailed information see PCM600 online
help.
The LCT indication is cleared in the same way as other indications. If composition data is
not collected with PCM600, the indication reappears after protection relay's reboot.
If the LCT indication appears, update the protection relay composition to
avoid information mismatch. The LCT indication does not affect the
functionality of the protection relay.
1MAC054853-MB B Section 8
Commissioning
615 series ANSI 147
Operation Manual