2
1
A070816 V2 EN
Figure 5: RJ-45 communication port and indication LEDs
1 Uplink LED
2 Communication LED
When a computer is connected to the protection relay, the relay's DHCP server for the
front interface assigns an IP address to the computer. The fixed IP address for the front port
is 192.168.0.254.
3.3 Web HMI
The WHMI allows secure access to the protection relay via a Web browser. The supported
Web browser versions are Internet Explorer 9.0, 10.0 and 11.0. When the Secure
Communication parameter in the protection relay is activated, the Web server is forced to
take a secured (HTTPS) connection to WHMI using TLS encryption.The WHMI is
verified with Internet Explorer 11.0.
WHMI is disabled by default. To enable the WHMI, select Main Menu/
Configuration/HMI/Web HMI mode via the LHMI. Reboot the
protection relay for the change to take effect.
WHMI offers several functions.
Programmable LEDs and event lists
System supervision
Parameter settings
Measurement display
DFR records
Fault records
Load profile record
Phasor diagram
Section 3 1MAC054853-MB B
615 series overview
28 615 series ANSI
Operation Manual