Section 6 Operating procedures
6.1 Monitoring
6.1.1 Indications
The operation of the protection relay can be monitored via three different indications on
the LHMI.
Three indicator LEDs with fixed functionality: Normal, Pickup and Trip
11 programmable LEDs
Information on the display
6.1.1.1 Monitoring indication messages
Indication messages and tripping data are shown in a dialog box. Only one dialog box can
be shown at a time, therefore the relay has internal priority for indication messages and
tripping data. Internal fault and warning messages have always higher priority than start
or trip information. Trip information has always higher priority than start information.
1. Read the indication message in the dialog box.
The message can indicate the pickup or tripping of protection functions or an internal
fault in the device.
2.
Press
to close the indication message without clearing it or press to activate
the Clear view and to clear messages.
1MAC054853-MB B Section 6
Operating procedures
615 series ANSI 89
Operation Manual