EasyManua.ls Logo

ABB Relion 670 series - Frequency Reporting

ABB Relion 670 series
944 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IEC140000146-1-en.vsd
PHASOR1
PHASOR2
PHASOR32
ANALOG1
ANALOG2
ANALOG24
FREQTRIG
DFDTTRIG
MAGHIGHTRIG
MAGLOWTRIG
BINARY1
BINARY2
BINARY24
PMUREPORT1
SMAI
SMMI
MEAS.
TRM
MU
TRM
MIM
PROTECTION
OP
UP
OC
UV
OR
NUM
IEEEC37.118 / 1344
messages
U/I samples
BIM
GPS /
IRIG-B
PPS time data
U
I
U
I
I/P
8 TCP
6 UDC
IEC140000146 V2 EN
Figure 38: Overview of reporting functionality (PMUREPORT)
The TRM modules are individually AC-calibrated in the factory. The calibration data is
stored in the prepared area of the TRM EEProm. The pre-processor block is extended with
calibration compensation and a new angle reference method based on timestamps. The
AI3P output of the preprocessor block is used to provide the required information for each
respective PMUREPORT phasor channel. More information about preprocessor block is
available in the section Signal matrix for analog inputs SMAI.
6.2.3.1 Frequency reporting
By using patented algorithm the IED can track the power system frequency in quite wide
range from 9 Hz to 95 Hz. In order to do that, the three-phase voltage signal shall be
connected to the IED. Then IED can adapt its filtering algorithm in order to properly
measure phasors of all current and voltage signals connected to the IED. This feature is
essential for proper operation of the PMUREPORT function or for protection during
generator start-up and shut-down procedure.
Section 6 1MRK 506 369-UUS -
Wide area measurement system
118 Line distance protection REL670 2.2 ANSI
Application manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals