AngleRCA
Forward
Area
Iop = I2
Vpol=-V2
Reverse
Area
ANSI10000031-1-en.vsd
ANSI10000031 V1 EN
Figure 274: Relay characteristic angle given in degree
In a transmission network a normal value of RCA is about 80°.
VPolMin: Minimum polarization (reference) voltage % of VBase.
I>Dir: Operate residual current level for directional comparison scheme. The setting is
given in % of IBase. The pickup forward or pickup reverse signals can be used in a
communication scheme. The appropriate signal must be configured to the communication
scheme block.
9.6 Sensitive directional residual overcurrent and power
protection SDEPSDE (67N)
Section 9 1MRK 506 369-UUS -
Current protection
528 Line distance protection REL670 2.2 ANSI
Application manual