EasyManua.ls Logo

ABB Relion 670 series - High Speed Distance Protection for Series Compensated Lines ZMFCPDIS (21); Identification

ABB Relion 670 series
944 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3I0Enable_PG
This setting opens up an opportunity to enable phase-to-ground measurement for phase-
to-phase-ground faults. It determines the level of residual current (3I0) above which
phase-to-ground measurement is activated (and phase-to-phase measurement is blocked).
The relations are defined by equation
334.
0 max
3I0Enable _ PG
3
100
ph
I
I I× ³ ×
EQUATION2548-ANSI V1 EN (Equation 334)
Where:
3I0Enable_PG
the setting for the minimum residual current needed to enable operation in the phase-to-
ground fault loops in %
I
phmax
the maximum phase current in any of the three phases
By default, this setting is set excessively high to always enable phase-to-phase
measurement for phase-to-phase-ground faults. This default setting value must be
maintained unless there are very specific reasons to enable phase-to-ground
measurement. Even with the default setting value, phase-to-ground measurement is
activated whenever appropriate, like in the case of simultaneous faults: two ground faults
at the same time, one each on the two circuits of a double line.
One specific situation where the 3I0Enable_PG setting should be altered is for cross-
country faults in high impedance grounded networks, in order to make sure that operation
is phase-to-ground. This is particularly important when using phase preference logic,
since it is only working per phase, not for phase-to-phase measurement. The limit should
be set so that it will be exceeded during a cross-country fault.
8.13 High speed distance protection for series compensated
lines ZMFCPDIS (21)
8.13.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
High speed distance protection zone
(zone 1-6)
ZMFCPDIS
S00346 V1 EN
21
1MRK 506 369-UUS - Section 8
Impedance protection
Line distance protection REL670 2.2 ANSI 383
Application manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals